T-Series Enclosure Heater

T-Series enclosure heaters are designed with standard redundant internal protection for long trouble free operation. The T-Series heater provides approved hazardous area heaters for a wide range of applications from instrument freeze protection to temperature maintenance for analytical applications. The system is highly configurable and includes redundant internal protection for long trouble free operation. Standard temperature ratings and operating voltages are listed below.

The T-Series heater can be configured for vertical and horizontal installation with maximum efficiency. It is available in two base sizes and variable fin area depending upon wattage and maintain temperature.

This heater series is available in T2, T3 and T4 temperature ranges to meet the needs of your area classification. It can be supplied with a factory set tamper proof temperature switch or connected to an existing or customer supplied controller. The standard junction box volume can be increased to accommodate other wiring connections such as impulse line heater cables.

Specifications

 Wattage

Up to 400 watts / unit for T3, Up to 600 watts / unit for T2

Supply Voltage

115, 230 and 277VAC (special order 12 & 24VDC, and 100 & 208VAC)

Classifications 

NEC & CSA: Class I Division 1 Group A, B, C, & D (T2 or T3; ATEX Zone I EEx d IIC T3), 

Mounting

 Variable positioning

Control Options

Tamper Proof Thermostat - 50ºF/10ºC, 75ºF/25ºC, 100ºF/40ºC, 125ºF/50ºC, 150ºF/6 

 

 


 


EH_TSERIES_GROUP_PH









 

 

   
  ISO 9001:2000
Registered